APR 160 and APR 400 disconnector

They are used to protect low voltage lines. The device is both a disconnector and a fuse. The design allows the disconnector to be operated from the ground thanks to the operating rod.

APR 160-X vs APR 400-X Table
Model APR160-X APR400-X
Rated switching voltage [V] 415 500
Number of poles 1, 3, 4 1, 3, 4
Nominal frequency [Hz] 50z 50
Rated insulation voltage [V] 1000 1000
Rated impulse voltage [kV] 6 12
Rated continuous current [A] 160 400
Nominal current for armature [A] 160 400
Rated switching current [A] 160 400
Conventional thermal current [A] 160 400
Conventional short circuit current [kA] 50 100
Rated work continuous continuous
Category of use AC22B AC22B
Fuse link size NH00 NH1 NH2
Degree of contamination PD3 PD3
Degree of protection IP23 IP23
Connected cross-sections Al/Cu wires 2 x (16-150mm²) 2 x (50-240mm²)
Connection durability 200 connections 200 connections
Mechanical durability 1600 cycles 1600 cycles

X – number of poles (1, 3, or 4).

Compliant with standards: PN-EN 60947-3 and PN-EN 60947-1.